1,200
VA
1,080
W
523.07
VAR
—
°
1,200
VA
1,080
W
523.07
VAR
—
°
Single-phase AC power is the most common form of electrical power delivered to homes and small commercial buildings in North America (120 V / 240 V) and internationally (230 V). Unlike DC circuits where power is simply P = VI, single-phase AC circuits require accounting for the power factor — the cosine of the phase angle between voltage and current waveforms — when the load contains inductive or capacitive elements.
There are three types of power in an AC circuit: real power (P), measured in watts, which does useful work such as heating or driving motors; reactive power (Q), measured in volt-amperes reactive (VAR), which is stored and released by inductors and capacitors; and apparent power (S), measured in volt-amperes (VA), which is the product of RMS voltage and RMS current as seen by the source.
The power triangle illustrates the relationship between these three quantities: S² = P² + Q², with P = S × cos(φ) and Q = S × sin(φ), where φ is the phase angle. The power factor PF = P/S = cos(φ) ranges from 0 (purely reactive load) to 1 (purely resistive load). A power factor of 1 means all apparent power does useful work; lower values mean the source must supply more current than the load actually uses for real work, increasing distribution losses.
For residential loads like incandescent lamps and electric heaters, PF ≈ 1. Motors, transformers, and fluorescent lighting typically have PF between 0.7 and 0.95. Industrial facilities are often penalized by utilities for low power factor below 0.95, incentivizing the installation of power factor correction capacitors.
This calculator is essential for sizing generators, inverters, UPS systems, transformers, and electrical panels. A generator rated at 10 kVA can supply at most 8 kW of real power to a load with PF = 0.8. Undersizing based on watts alone, ignoring the VA rating, is a common and costly mistake that leads to generator overloads and premature failure.
In household wiring, the 120 V / 15 A outlet is rated at 1,800 VA of apparent power. If the connected load has PF = 0.85 (typical for a refrigerator compressor), the available real power is only 1,530 W — a practical limit that must be respected when calculating circuit loading.
The phase angle output tells you by how many degrees the current lags (inductive load) or leads (capacitive load) the voltage. This is critical for troubleshooting power quality issues and for configuring automatic power factor correction systems.
Apparent power S = V × I (VA). Real power P = S × PF = V × I × cos(φ) (W). Reactive power Q = S × sin(φ) = S × sin(arccos(PF)) (VAR). Phase angle φ = arccos(PF) in degrees. The power triangle relationship S² = P² + Q² is always satisfied.
Real power (W) is what you pay for on your electricity bill. Apparent power (VA) determines cable and equipment sizing. Reactive power (VAR) represents energy cycling back and forth without doing work. A low power factor (below 0.9) increases apparent power relative to real power, requiring larger conductors and equipment.
Inputs
Results
A 120 V air conditioner drawing 12 A at PF = 0.85 consumes 1,224 W real power but demands 1,440 VA from the supply, with 757 VAR reactive component.
Inputs
Results
A 5 kW electric water heater is a pure resistive load — all VA converts to watts, reactive power is zero, and phase angle is 0°.
Resistive loads (heaters, incandescent bulbs): PF ≈ 1.0. Refrigerators and air conditioners: PF ≈ 0.8–0.9. Older fluorescent lights: PF ≈ 0.5–0.6. LED drivers and modern electronics often have PF correction, achieving PF > 0.95.
Low power factor means higher current for the same real power. Higher current causes more I²R losses in wiring, requires larger cable cross-sections, and stresses transformers. Utilities often add power factor surcharges for commercial customers with PF below 0.95.
Unity power factor (PF = 1.0) means voltage and current are perfectly in phase — the load is purely resistive. All of the apparent power does useful work, and reactive power is zero. This is the ideal condition for maximum power transfer efficiency.
Install power factor correction capacitors to offset the lagging current drawn by inductive loads (motors, transformers). The capacitors supply reactive power locally, reducing the reactive current drawn from the source. Synchronous motors can also provide leading reactive power.
kW measures real (useful) power. kVA measures apparent power (V × I regardless of phase). kW = kVA × PF. Generators and UPS systems are rated in kVA because their output current capacity is fixed regardless of the load's power factor.
No. Power factor is defined as the ratio of real to apparent power, with a maximum value of 1.0 for purely resistive loads. Values above 1 would violate energy conservation. Some meters display 'apparent power factor' accounting for harmonic distortion (displacement PF vs. true PF).
Non-linear loads (variable frequency drives, switching power supplies, LED drivers) draw non-sinusoidal current, producing harmonic distortion. True power factor = displacement PF × distortion factor. THD (total harmonic distortion) degrades power quality and must be considered alongside displacement PF.
Roboculator Team
The Roboculator Team explains calculations, planning tools, and practical formulas in clear language for real-life situations.
How helpful was this calculator?
Be the first to rate!
Ohm's Law Calculator
Basic Electrical & Ohm's Law Calculators
DC Power Calculator
Basic Electrical & Ohm's Law Calculators
Three Phase Power Calculator
Basic Electrical & Ohm's Law Calculators
Split Phase Power Calculator
Basic Electrical & Ohm's Law Calculators
Power Factor Calculator
Basic Electrical & Ohm's Law Calculators
Resistance Calculator
Basic Electrical & Ohm's Law Calculators