—
W
—
W
2,736
W
—
W
3
A
—
W
—
W
2,736
W
—
W
3
A
Split-phase power is the standard residential electrical service in North America, providing both 120 V (for general outlets and lighting) and 240 V (for large appliances) from a single-phase transformer secondary. The term 'split-phase' refers to the transformer secondary winding being center-tapped, creating two 120 V legs (L1 and L2) that are 180° out of phase with each other and a neutral at center potential.
The standard residential service panel receives three conductors from the utility transformer: L1 (120 V to neutral), L2 (120 V to neutral, 180° out of phase with L1), and a neutral (N). Between L1 and L2 the voltage is 240 V, used for electric dryers, ranges, water heaters, central air conditioners, and EV chargers. The neutral carries the difference current between L1 and L2 loads.
Understanding split-phase power is essential for residential electricians, homeowners planning circuit additions, and engineers sizing service entrance equipment. A 200 A split-phase service delivers a maximum of 200 A on each leg, for a total apparent power of 200 A × 240 V = 48 kVA. However, the actual usable power depends on the balance of loads across L1 and L2 and their power factors.
The neutral current is the vector difference of L1 and L2 currents. For balanced loading (equal currents on both legs), the neutral carries zero current — the ideal condition that minimizes neutral conductor heating and voltage imbalance. When loads are heavily unbalanced, the neutral must carry the full difference current, which is why the neutral conductor in residential wiring is sized the same as the line conductors.
For 240 V-only loads (water heaters, EV chargers), current flows from L1 through the load to L2 with no neutral connection. Both legs carry equal current, and neutral current is zero for that load. The power calculation for such loads uses the full 240 V: P = 240 × I × PF.
Load balancing across the two legs of a split-phase service is good electrical practice. Panel manufacturers typically alternate circuit breaker positions to encourage balanced loading, but the final distribution depends on which circuits are loaded simultaneously. Electricians use a clamp meter to measure L1 and L2 currents at the panel and rearrange circuits if imbalance exceeds 10%.
L1 power = 120 V × I_L1 × PF. L2 power = 120 V × I_L2 × PF. Total power = P_L1 + P_L2. Neutral current = |I_L1 - I_L2|. The 240 V load power uses min current since both legs must equal for a true 240 V load; this field estimates the 240 V portion contribution.
Minimize neutral current by balancing loads across L1 and L2. Neutral current above 50% of line current indicates significant load imbalance. A neutral current near zero means both legs are equally loaded — optimal for panel and transformer efficiency. Total power is the sum of all loads on both legs.
Inputs
Results
A home drawing 80 A on L1 and 65 A on L2 at PF = 0.9 consumes 15.66 kW total with a 15 A neutral current — somewhat unbalanced, redistributing loads could eliminate most neutral current.
Inputs
Results
Perfectly balanced loading of 50 A on each leg at unity PF delivers 12 kW total with zero neutral current — the ideal operating condition.
Split-phase uses a single-phase transformer secondary with a center tap, providing 120 V and 240 V from two conductors plus neutral. Three-phase uses three separate phase conductors displaced 120° apart. Split-phase is standard for residential service in North America; three-phase is used for commercial and industrial power.
The 120 V standard (originally 110 V) was established by Thomas Edison and remained dominant in North America for compatibility. Europe standardized at 230 V (higher voltage = lower current = smaller wire for same power). The center-tap arrangement allows both voltages from a single transformer winding.
Electric dryers, ranges, ovens, water heaters, central air conditioners, heat pumps, EV chargers (Level 2), well pumps, and some power tools. These high-power appliances use 240 V to halve the current compared to 120 V, allowing smaller wire gauges.
A lost neutral (open neutral) is dangerous. Voltage across 120 V loads re-balances based on load resistance, causing some loads to see overvoltage (potentially > 150 V) and others undervoltage. This can destroy sensitive electronics. The NEC requires main bonding jumpers and grounding electrode systems to mitigate this risk.
Use a clamp meter at the main panel to measure L1 and L2 currents during typical use. The neutral current equals the difference. Alternatively, measure neutral current directly at the main neutral conductor. Imbalance exceeding 10% of service ampacity warrants load redistribution.
NEC requires GFCI protection for 240 V outlets in bathrooms, garages, outdoors, and kitchens. Double-pole GFCI breakers monitor both L1 and L2 and trip if differential current exceeds 5 mA, protecting against ground faults on either leg of 240 V loads.
Roboculator Team
The Roboculator Team explains calculations, planning tools, and practical formulas in clear language for real-life situations.
How helpful was this calculator?
5.0/5 (1 rating)
Ohm's Law Calculator
Basic Electrical & Ohm's Law Calculators
DC Power Calculator
Basic Electrical & Ohm's Law Calculators
Watts / Amps / Volts Calculator (Single Phase)
Basic Electrical & Ohm's Law Calculators
Three Phase Power Calculator
Basic Electrical & Ohm's Law Calculators
Power Factor Calculator
Basic Electrical & Ohm's Law Calculators
Resistance Calculator
Basic Electrical & Ohm's Law Calculators