83.138
kVA
74.825
kW
83,138
VA
1.203
A/kVA
83.138
kVA
74.825
kW
83,138
VA
1.203
A/kVA
The kVA Calculator computes the apparent power in kilovolt-amperes (kVA) from voltage and current for three-phase electrical systems, and shows the equivalent kW at common power factor values. kVA is the fundamental rating unit for generators, transformers, UPS systems, and switchgear, making this one of the most frequently used calculations in electrical engineering.
For three-phase systems, apparent power S (kVA) = √3 × VL × IL / 1000, where VL is line-to-line voltage and IL is line current. The √3 factor (≈1.732) accounts for the phase relationship between three voltage vectors 120° apart. For single-phase systems, S = V × I / 1000 without the √3 factor.
The distinction between kVA and kW matters enormously in electrical design. A generator rated 1000 kVA can supply a maximum of 800 kW at 0.8 PF, or 900 kW at 0.9 PF, or 1000 kW at unity PF. If your load is 900 kW at 0.8 PF, you need 900/0.8 = 1125 kVA of generation capacity — not just 900 kVA. Undersizing generators for kVA is a common and costly mistake.
Similarly, transformer ratings in kVA represent the maximum continuous current-handling capacity. The transformer windings heat based on current (I²R), not active power. A 500 kVA transformer supplying 400 kW at 0.8 PF is fully loaded (400/0.8 = 500 kVA). It cannot supply an additional 100 kW of purely resistive load (unity PF) without overloading.
UPS systems are universally rated in kVA because their inverters and battery systems must supply the full volt-ampere product. Battery sizing, inverter current rating, and bypass switch sizing all depend on kVA, not kW. Power factors of typical UPS loads vary widely — servers and networking equipment typically 0.9-0.99 PF, while older computer equipment may be 0.6-0.7 PF.
Three-phase: S = √3 × V_L × I_L / 1000 (kVA). This formula uses line-to-line voltage (the voltage measured between any two phases) and line current. Single-phase: S = V × I / 1000. Active power P = S × PF. This calculator assumes three-phase throughout; for single-phase results, divide kVA by √3.
Use kVA result to: select transformer rating (use next standard size above calculated kVA plus 20% margin), size generator (add starting kVA for largest motor), select UPS (match or exceed total kVA of connected loads). For kW-specified equipment, kVA = kW / PF. Standard transformer sizes: 25, 37.5, 50, 75, 100, 167, 250, 333, 500, 750, 1000 kVA.
Inputs
Results
166 kVA load. At 0.80 PF (typical industrial), this represents 133 kW of real power. Select a 167 kVA or 250 kVA transformer with margin.
Inputs
Results
10.8 kVA PDU. IT equipment at 0.9 PF delivers 9.7 kW of actual IT load. A 10 kVA UPS would be marginally adequate; 15 kVA recommended.
In a balanced three-phase system, the power delivered by all three phases combined is P = 3 × V_phase × I_line × PF. Since V_phase = V_line/√3, substituting: P = 3 × (V_line/√3) × I × PF = √3 × V_line × I × PF. The √3 consolidates three single-phase equations using line (not phase) voltage.
kW (active power): does real work (heat, motion, light). kVAR (reactive power): oscillates between source and reactive loads, no net work. kVA (apparent power) = √(kW² + kVAR²): total volt-ampere product, determines equipment current ratings. PF = kW/kVA relates them.
Step 1: Sum all continuous loads in kW and kVAR. Step 2: Calculate total kVA = √(P²+Q²). Step 3: Add starting kVA for the largest motor (typically 3-6× motor kVA during starting). Step 4: Apply service factor (1.25 minimum). Step 5: Select next standard generator size above total. Also verify the generator's PF rating matches your load PF.
Transformers can sustain overloads for short periods depending on thermal time constant and pre-load temperature. IEEE C57.91 provides loading guides: a transformer at 50% load can sustain 140% of rated kVA for 4 hours; at 100% pre-load, only 110% for short periods. Thermal protection relays enforce limits automatically.
For a single phase-to-neutral load at 277V (on a 480V three-phase system): kVA = 277 × I / 1000. This load appears in only one phase, causing unbalance. Convert to three-phase kVA for transformer sizing: divide by 3 to get per-phase kVA, then multiply by 3 for total three-phase impact (same result, but must track phase balance).
Roboculator Team
The Roboculator Team explains calculations, planning tools, and practical formulas in clear language for real-life situations.
How helpful was this calculator?
Be the first to rate!
Energy Consumption Calculator
Power & Energy Calculators
Power Factor Correction Calculator
Power & Energy Calculators
BTU / Kilowatt Converter
Power & Energy Calculators
kW to Amps Calculator
Power & Energy Calculators
Power Loss Calculator (Joule Effect)
Power & Energy Calculators
Capacitor Bank Sizing Calculator
Power & Energy Calculators