20
kVAR
1,989.44
μF
144.34
A
28.87
A
1.6
Ω
0.357
mH
20
kVAR
1,989.44
μF
144.34
A
28.87
A
1.6
Ω
0.357
mH
The Capacitor Bank Sizing Calculator determines the capacitance value per phase, per-step kVAR, rated current, and detuning reactor size for a three-phase automatic power factor correction (APFC) capacitor bank. Properly sized capacitor banks are the primary tool for reactive power compensation in industrial and commercial electrical systems.
A capacitor bank consists of three-phase capacitor units connected to the electrical bus, typically in delta (Δ) or star (Y) configuration. Delta-connected capacitors are exposed to full line-to-line voltage but are easier to switch and provide better harmonic performance. Star-connected banks are common in high-voltage applications. This calculator uses the phase voltage approach valid for balanced three-phase systems.
The required capacitance per phase is derived from: Q = V²/XC = V² × ωC, so C = Q/(ω × V² × 3) per phase for a three-phase star-connected bank. The capacitive reactance XC = Vphase² × 3 / Q determines the resonant frequency with any system inductance.
Detuning reactors (series inductors) are critically important in systems with harmonic loads. Without detuning, capacitors can resonate with system inductance at a harmonic frequency, causing catastrophic overcurrent. Detuning reactors are sized to place the LC resonant frequency below the lowest problematic harmonic. A 7% detuned reactor (p = 7%) creates resonance at 50/√0.07 = 189 Hz (between 3rd and 5th harmonics for 50 Hz systems). For 60 Hz systems, the detuning is designed similarly to avoid the 300 Hz (5th harmonic).
APFC panels typically include: a power factor relay (controller) that measures PF and switches capacitor steps as needed, vacuum contactors rated for capacitor switching (which involves high inrush currents), detuned capacitor modules (capacitor + reactor unit), and protection devices (fuses, thermal protection). Standard automatic banks range from 25 kVAR to over 1000 kVAR in modular designs.
Phase voltage V_ph = V_LL/√3. For three-phase star bank: Q_total = 3 × V_ph² × ωC. Solving for C: C = Q/(3 × V_ph² × ω). Capacitive reactance X_C = 1/(ωC). kVAR per step = total/steps. Capacitor current I = Q_total/(√3 × V_LL). Detuning reactor for 7%: X_L = 0.07 × X_C, so L = 0.07 × X_C / ω (mH).
Capacitance result is per phase for a star-connected bank. For delta connection, multiply C by 3. kVAR per step defines the resolution of the APFC system — smaller steps allow finer PF control but require more contactors. Capacitor current × 1.1 (110% overrating factor) determines contactor and fuse rating. Always specify capacitors rated for 10% above system voltage.
Inputs
Results
5 steps of 20 kVAR each. 994 μF per phase — specify 1000 μF / 240V rated capacitors. Detuning reactor: 0.057 mH per phase at 7% detuning.
Inputs
Results
50 kVAR steps provide good resolution. 601A capacitor current requires heavy-duty contactors. 10 steps allow 0-500 kVAR in 50 kVAR increments.
A detuned bank adds series inductors (reactors) to each capacitor unit. The LC combination has a resonant frequency set below the lowest problem harmonic (usually 5th). The reactor 'detunes' the circuit away from harmonic resonance. Standard detuning factors: 5.67% (resonance at 210 Hz / 3.5th harmonic), 7% (189 Hz), 14% (134 Hz).
Fixed banks suit constant loads where reactive power demand doesn't vary much (e.g., a single large motor running continuously). Automatic (APFC) banks suit variable loads — commercial buildings, manufacturing plants with multiple shifts. APFC prevents over-correction during light loading, which can raise voltage and damage equipment.
Overvoltage (exceeds capacitor voltage rating — occurs on harmonic resonance or voltage swells), harmonic overcurrent (resonance without detuning), transient overcurrent during switching (mitigated by pre-charge circuits or zero-voltage switching contactors), thermal degradation from ambient temperature, and capacitor aging (dielectric breakdown over time).
Capacitor kVAR is proportional to V². At nominal voltage, delivered kVAR equals nameplate. At ±5% voltage: kVAR changes by (1±0.05)² = ±10.25%. Low voltage reduces kVAR delivery, which may leave PF uncorrected during voltage sags. This must be considered in system design, especially near transformers with voltage regulation.
Annual inspection: check for swollen/bulging capacitor cans (sign of internal failure), clean ventilation filters, torque-check terminal connections, test capacitance with capacitance meter (should be within ±10% of nameplate), verify contactor operation, and check reactor condition. Replace capacitors that are ±10% below nameplate capacitance.
Roboculator Team
The Roboculator Team explains calculations, planning tools, and practical formulas in clear language for real-life situations.
How helpful was this calculator?
Be the first to rate!
Energy Consumption Calculator
Power & Energy Calculators
Power Factor Correction Calculator
Power & Energy Calculators
BTU / Kilowatt Converter
Power & Energy Calculators
kVA Calculator
Power & Energy Calculators
kW to Amps Calculator
Power & Energy Calculators
Power Loss Calculator (Joule Effect)
Power & Energy Calculators