10
100
V
10
A
100
10
100
V
10
A
100
The Transformer Turns Ratio Calculator determines the voltage transformation ratio, secondary voltage, secondary current, and impedance transformation ratio from the turns count and primary electrical quantities. The turns ratio is the most fundamental parameter of any transformer, governing all voltage, current, and impedance transformations between windings.
The turns ratio a = N1/N2 directly gives the voltage transformation: V2 = V1/a. For a step-down transformer with a = 10, a 1000V primary yields a 100V secondary. Current transforms inversely: I2 = I1 × a, preserving apparent power (V1I1 = V2I2 in an ideal transformer).
The impedance transformation ratio is a² — arguably the most important property for circuit analysis. An impedance ZL connected to the secondary appears as ZL × a² when referred to the primary. This impedance reflection technique is used extensively in audio transformers (matching amplifier output impedance to speaker impedance), RF transformers, and power system analysis.
In power engineering, the turns ratio is used for current transformer (CT) design — a CT with 600:5 ratio steps down line current by a factor of 120, allowing 5A-range instruments to measure high primary currents safely. Potential transformers (PTs/VTs) similarly step down high voltages for metering, typically to 110V or 120V secondary.
Measuring turns ratio in the field uses a turns ratio tester (TTR) that applies a low AC voltage to one winding and measures the other. Deviations from nameplate ratio indicate shorted turns, open circuits, or winding damage. Typical acceptance criteria for distribution transformers require turns ratio within 0.5% of nameplate value.
From Faraday's law: V = N × dΦ/dt. Both windings share the same core flux, so V1/V2 = N1/N2 = a. By conservation of energy (ideal): V1I1 = V2I2, so I2/I1 = N1/N2 = a. Impedance: Zprimary = V1/I1 = (a×V2)/(I2/a) = a² × V2/I2 = a² × Zsecondary.
a > 1: Step-down transformer (V2 < V1, I2 > I1). a < 1: Step-up transformer (V2 > V1, I2 < I1). a = 1: Isolation transformer. Impedance ratio a² matters for: matching amplifier to load, referring circuit elements between windings, and fault current calculations on secondary referred to primary.
Inputs
Results
a=14.1, a²=198.8. A 200Ω amplifier output matched to ~1Ω speaker via this transformer for maximum power transfer.
Inputs
Results
Turns ratio of 26.5 steps down 11kV to 415V. Secondary current is 26.5× higher than primary.
A Transformer Turns Ratio (TTR) tester applies 8V or 100V to one winding and measures the output of the other winding. The ratio is calculated digitally. Modern TTR testers also measure excitation current and phase angle, helping identify shorted turns or core problems.
Tap changers are connections to intermediate points on the primary winding, allowing the turns ratio to be adjusted by ±2.5% to ±10% in steps. Off-load tap changers require de-energizing; on-load tap changers (OLTC) can switch under load. Used to compensate for supply voltage variations and maintain secondary voltage.
Z = V/I. Secondary impedance Z₂ = V₂/I₂. Referred to primary: Z₂' = V₁/I₁ = (aV₂)/(I₂/a) = a² × V₂/I₂ = a²Z₂. The voltage scales by a and current scales by 1/a, so impedance (V/I) scales by a × a = a².
An autotransformer shares a common winding between primary and secondary — part of the winding serves both functions. The voltage ratio still equals the turns ratio for the relevant sections. Autotransformers are more compact and efficient but provide no galvanic isolation between primary and secondary.
A fault on the secondary (V₂ side) draws high current. This current reflected to the primary is reduced by factor a. For a 10:1 transformer with a 10kA secondary fault, primary fault contribution is ~1kA (plus source fault current). The transformer impedance further limits this current.
Roboculator Team
The Roboculator Team explains calculations, planning tools, and practical formulas in clear language for real-life situations.
How helpful was this calculator?
Be the first to rate!
Motor Full Load Current Calculator
Motor & Transformer Calculators
Motor Circuit Protection Calculator
Motor & Transformer Calculators
Motor Overload Protection Calculator
Motor & Transformer Calculators
Single Phase to Three Phase Converter Calculator
Motor & Transformer Calculators
Motor Speed Calculator (RPM)
Motor & Transformer Calculators
Motor Slip Calculator
Motor & Transformer Calculators