1
AWG
0
kcmil-equiv
0
cmil
250,122
1
1
AWG
0
kcmil-equiv
0
cmil
250,122
1
The grounding conductor sizing calculator determines the minimum size for Equipment Grounding Conductors (EGC) and Grounding Electrode Conductors (GEC) per NEC Article 250. Proper grounding conductor sizing is critical for electrical safety — in the event of a ground fault, the EGC must carry sufficient fault current to trip the overcurrent protective device (breaker or fuse) quickly, limiting shock hazard and preventing fires.
NEC Table 250.122 specifies minimum copper EGC sizes based on the rating of the overcurrent protective device protecting the circuit. For a 20A breaker, a minimum AWG 12 copper EGC is required. For a 100A breaker, AWG 8 copper. For a 400A breaker, AWG 3 copper. Aluminum EGC sizes are two AWG numbers larger (lower ampacity per unit area) than copper.
The EGC serves two critical functions. First, it provides a low-impedance fault return path so that ground faults cause the breaker to trip quickly rather than leaving energized conductors accessible. Second, it bonds metal enclosures, conduit, and equipment frames to ground potential, preventing dangerous touch voltages. Without proper EGC sizing, a high-impedance fault might not trip the breaker, leaving equipment energized at dangerous voltages indefinitely.
The GEC (Grounding Electrode Conductor) connects the service neutral and equipment ground to the grounding electrode system (ground rods, metal water pipe, concrete-encased electrode, etc.). NEC Table 250.66 sizes the GEC based on the largest service entrance conductor, not the OCPD rating. This is a common area of confusion — EGC sizing uses Table 250.122 (OCPD-based) while GEC sizing uses Table 250.66 (service conductor-based).
When the supply conductors are increased in size for any reason (e.g., voltage drop), the EGC must also be proportionally increased per NEC 250.122(B). The EGC must not be smaller than the minimum from Table 250.122, and if supply conductors are larger than required by ampacity, the EGC increases proportionally.
EGC minimum size is looked up from NEC Table 250.122 based on the OCPD rating. For copper: ≤15A = AWG 14, ≤20A = AWG 12, ≤30-60A = AWG 10, ≤100A = AWG 8, ≤200A = AWG 6, ≤300A = AWG 4, ≤400A = AWG 3, ≤500A = AWG 2, ≤600A = AWG 1, ≤800A = AWG 1/0, ≤1000A = AWG 2/0. Aluminum is two sizes larger.
The minimum AWG from the table must not be exceeded (made smaller). If supply conductors are upsized beyond ampacity requirements, the EGC must be proportionally enlarged per NEC 250.122(B): new EGC CM = Table EGC CM × (actual supply CM / required supply CM). Always verify the EGC is physically protected within the raceway and connected at both ends.
Inputs
Results
A 20A circuit requires minimum AWG 12 copper EGC per NEC Table 250.122. Use green or bare conductor in the same raceway as the phase conductors.
Inputs
Results
A 200A service requires minimum AWG 6 copper EGC (Table 250.122) and AWG 4 copper GEC per Table 250.66 for #3 AWG service entrance conductors.
EGC (Equipment Grounding Conductor) bonds equipment enclosures and runs with each circuit back to the panel. GEC (Grounding Electrode Conductor) connects the service neutral and main bonding jumper to the grounding electrode system (earth). EGC sized by NEC Table 250.122; GEC by Table 250.66.
Yes — steel conduit (EMT, IMC, RMC) installed with proper connections serves as an EGC per NEC 250.118. PVC conduit cannot serve as an EGC — a separate grounding conductor is required inside PVC.
No — the EGC carries current only during ground fault conditions. It is not a normal current-carrying conductor and should not be confused with the neutral conductor, which carries return current during normal operation.
An undersized EGC may have too much resistance to allow sufficient fault current to trip the breaker quickly. The fault may remain energized for dangerously long periods, causing severe shock hazard and fire risk.
Per NEC 250.122(B), when the ungrounded (phase) conductors are increased above minimum ampacity size, the EGC must be proportionally enlarged. Calculate: new EGC area = Table EGC area × (actual conductor area / minimum required conductor area).
Per NEC 250.119, EGCs must be bare, green, or green with yellow stripes. Conductors AWG 6 and larger may be identified with green tape at termination points rather than being continuously green.
Roboculator Team
The Roboculator Team explains calculations, planning tools, and practical formulas in clear language for real-life situations.
How helpful was this calculator?
Be the first to rate!
Wire Size Calculator
Wiring & Conduit Sizing Calculators
Voltage Drop Calculator
Wiring & Conduit Sizing Calculators
Conduit Fill Calculator
Wiring & Conduit Sizing Calculators
Wire Resistance Calculator
Wiring & Conduit Sizing Calculators
Maximum Wire Length Calculator
Wiring & Conduit Sizing Calculators
NEC Wire Size Calculator
Wiring & Conduit Sizing Calculators