Roboculator
Online CalculatorsCategoriesDate & EventsNews
Get Started
Online CalculatorsCategoriesDate & EventsNewsGet Started
Roboculator

Smart calculators for every challenge. Free, fast, and private.

Categories

  • Finance
  • Health
  • Math
  • Construction
  • Conversion
  • Everyday Life

Popular Tools

  • Date & Events
  • Loan Calculator
  • BMI Calculator
  • Percentage Calc
  • Latest News
  • Search All

Resources

  • Glossary
  • Topic Tags
  • News & Insights

Company

  • About
  • Contact

Legal

  • Privacy Policy
  • Terms of Service
  • Editorial Policy
  • Disclaimer
© 2026 Roboculator. All rights reserved.
Roboculator

roboculator.com

  1. Home
  2. /Electrical
  3. /Short Circuit & Fault Current Calculators
  4. /Circuit Breaker Sizing Calculator (Fault)

Circuit Breaker Sizing Calculator (Fault)

Calculator

Results

Minimum Breaker Rating

125

A

Recommended Standard Breaker Rating

0

A

Required Interrupting Capacity

27.5

kA

Recommended Standard AIC Rating

0

kA

Breaker Oversize vs Minimum

0

%

Results

Minimum Breaker Rating

125

A

Recommended Standard Breaker Rating

0

A

Required Interrupting Capacity

27.5

kA

Recommended Standard AIC Rating

0

kA

Breaker Oversize vs Minimum

0

%

The Circuit Breaker Sizing Calculator (Fault) determines the minimum circuit breaker trip rating and required interrupting capacity (AIC — Ampere Interrupting Capacity) based on load current and available fault current. Selecting a circuit breaker with inadequate trip rating or insufficient fault interrupting capacity is a serious safety violation that can result in catastrophic failure during a fault event.

Circuit breaker selection involves two independent but equally critical parameters. The trip rating (continuous current rating) must be equal to or greater than the maximum expected load current, adjusted for load type. For continuous loads (loads that operate for 3 hours or more continuously), NEC 210.20(A) requires the breaker be rated at 125% of the continuous current. The interrupting rating must equal or exceed the available fault current at the installation point — this is a non-negotiable safety requirement per NEC 110.9.

Standard MCCB (Molded Case Circuit Breaker) interrupting ratings in North America include: 10 kA, 14 kA, 18 kA, 22 kA, 25 kA, 35 kA, 42 kA, 65 kA, 85 kA, and 100 kA. The required AIC must be met or exceeded — using a 22 kA-rated breaker in a location with 25 kA available fault current is a code violation and safety hazard. The breaker may fail to interrupt the fault, resulting in a sustained arc that can cause fire, explosion, and severe injury.

When available fault current exceeds the breaker's interrupting rating, engineers have several options: series rating (placing a current-limiting fuse upstream to limit let-through to within the breaker's rating — permitted by UL 489 and NEC 240.86 under specific conditions), replacing the breaker with a higher-rated model, adding impedance upstream (transformer or cable) to reduce available fault current, or using current-limiting circuit breakers that limit fault current in the first half-cycle.

The arc flash hazard analysis (IEEE 1584) depends on available fault current — higher fault current at a given location results in higher arc flash incident energy. Selecting appropriate arc flash PPE categories and establishing flash protection boundaries requires accurate fault current data at every bus in the system. Undersized or improperly selected breakers compromise both personnel safety and arc flash analysis validity.

For motor circuits, NEC Article 430 permits breaker trip ratings up to 250% of motor FLA (for instantaneous trip breakers) to allow for starting current. The maximum trip setting is governed by the motor's service factor and the type of breaker (thermal-magnetic MCCB versus electronic trip or motor circuit protector). This calculator uses a simpler load-type multiplier for general guidance — always verify against NEC Article 430 tables for motor applications.

Visual Analysis

How It Works

Minimum trip = FLC × load_type_factor (1.0 for resistive, 1.25 for continuous, 1.5-2.5 for motor start). Recommended trip adds 25% margin for conservative selection. Required AIC = prospective fault current (kA) at the installation point. Minimum AIC to select rounds up to the next standard interrupting rating above the required value.

Understanding Your Results

Select a breaker with: trip rating ≥ minimum trip, AIC rating ≥ required AIC. Both conditions are mandatory. The recommended trip (with added margin) accounts for load growth and measurement uncertainty. Always verify the breaker's AIC rating at the actual system voltage — some breakers have lower ratings at higher voltages. Check NEC 240.86 for series rating requirements if using fuse-breaker series combinations.

Worked Examples

100A Continuous Load, 25 kA Fault at 480V

Inputs

load current a100
fault current ka25
load type1.25
voltage v480

Results

minimum trip a125
recommended trip a156.25
required aic ka25
min interrupting ka30

Select 150A or 175A trip breaker (next standard sizes above 156A). AIC must be ≥ 30 kA. A standard 25 kA MCCB is insufficient — upgrade to 35 kA AIC minimum.

50 HP Motor Circuit at 480V, 35 kA Fault

Inputs

load current a65
fault current ka35
load type1.5
voltage v480

Results

minimum trip a97.5
recommended trip a121.875
required aic ka35
min interrupting ka40

50 HP motor (~65A FLA). Motor factor 1.5× → 98A minimum. Select 100A trip, motor circuit protector. Fault requires 42 kA AIC minimum (next standard above 40 kA calculated).

Frequently Asked Questions

The breaker may fail to interrupt the fault — the arc inside the breaker cannot be extinguished. This results in a sustained arc that can: explode the breaker housing, cause severe burns and blast pressure to nearby personnel, ignite surrounding materials causing fire, and leave the fault current flowing until an upstream device (fuse or main breaker with adequate AIC) clears the fault. This scenario is called 'breaker failure' and is extremely dangerous.

Series rating (UL 489, NEC 240.86) allows a combination of a current-limiting fuse upstream and a lower-AIC breaker downstream. The fuse limits let-through current to within the breaker's interrupting capacity. The series combination must be tested and listed by a recognized lab (UL, ETL). Series ratings allow cost-effective breaker selection in high-fault-current panels without replacing all breakers with higher-rated units.

All refer to the same concept — maximum fault current the device can safely interrupt. AIC (Ampere Interrupting Capacity) and AIR (Ampere Interrupting Rating) are the same, with AIR being the more precise NEMA/UL terminology. kAIC simply expresses the value in kiloamperes. SCCR (Short Circuit Current Rating) is used for equipment assemblies (panels, motor control centers) rather than individual devices.

Most MCCBs are rated at multiple voltages. A breaker rated 65 kAIC at 240V may be rated only 18 kAIC at 480V. Always check the breaker's AIC at the actual system voltage. This voltage-dependent rating appears in the manufacturer's catalog in a table format. Using a breaker's 240V AIC rating in a 480V application is a dangerous mistake.

Thermal-magnetic MCCBs have: thermal element for overload (slow, heat-based), and magnetic element for short circuit (fast, instantaneous). Instantaneous trip setting determines the current level at which the magnetic trip operates. Electronic trip MCCBs provide: adjustable long-time (LT), short-time (ST), and instantaneous (I) settings, plus ground fault (GF) protection — offering precise coordination capability for complex systems.

Frame size is the physical enclosure rating (e.g., 400A frame). Trip rating is the actual current rating of the trip unit installed in that frame (e.g., 150A trip in a 400A frame). A single frame size can accommodate multiple trip ratings. The frame size determines maximum fault current duties; the trip rating determines continuous and overload performance. Breakers can often be re-tripped (larger trip unit installed) without replacing the frame.

Sources & Methodology

NFPA 70 NEC 2023 (Articles 110.9, 210.20, 240.86, 430), UL 489 (MCCBs), IEEE 1584 (Arc Flash), IEEE C37.13 (Low Voltage Switchgear), Square D Circuit Breaker Application Guide
R

Roboculator Team

The Roboculator Team explains calculations, planning tools, and practical formulas in clear language for real-life situations.

How helpful was this calculator?

Be the first to rate!

Related Calculators

Short Circuit Current Calculator

Short Circuit & Fault Current Calculators

Fault Current Calculator

Short Circuit & Fault Current Calculators

Cable Let-Through Energy Calculator

Short Circuit & Fault Current Calculators

Fuse Sizing Calculator

Short Circuit & Fault Current Calculators